Test Installation
Follow these procedures to verify you have correctly installed
the LS-60.
TO CHECK FAN (If you connected the G wire):
Press the fan button to turn the fan ON.
Verify that air is blowing from the system.
Press the fan button again to return to AUTO.
TO CHECK HEAT
Set the mode to HEAT by pressing the MODE button until HEAT is displayed.
Touch the temperature display to bring up the MANUAL screen.
Touch the + icon and raise the target temp to 90
o
F; allow the system 2 minutes to respond.
Verify that heat is blowing from the system. Return the Target Temperature to a nomal
setting.Return mode to OFF by pressing the mode button.
If you have a heat pump, leave in off for 4 minutes before checking COOL.
TO CHECK COOL (do not operate AC if the outside temp is below 65
o
F)
Set the mode to COOL by pressing the MODE button until COOL is displayed.
Touch the - icon and lower cool Target Temperature to 50
o
F.
Allow the system 5 minutes to respond.
Verify that cool air is blowing from the system.
Return mode to OFF.